- compact long-distance directional pickup
- Locates gas leaks and corona within inches of the source
- Lightweight for easy use, even in remote field locations
- Insensitive to high ambient audible noise levels
The Biddle Phase Sequence/Continuity Indicator provides positive identification of phase sequence of energized lines and indicates which phase, if any, is faulty.
Test Procedure Continuity: Connect red, yellow and blue leads to the phases A, B and C, respectively. If continuity is complete, the three top neon tubes will light. If continuity is not complete, only the faulty phase will light.
Phase Rotation Sequence: After continuity test indication is proven without a faulty phase, either of the two bottom neon tubes will light, indicating correct A-B-C rotation or incorrect A-C-B rotation. If necessary, reconnect to obtain A-B-C rotation.